ALL Type

Ezi-SERVO BT-28 Series

Status Monitor LED

1. LED Display
Status LED
Disable Green :  
Red :
Green light flashing, Red light of
Enable Green :  
Red :
Green light on, Red light of
Enable & Communication Green :  
Red :  
Green light on, Rlight flashing
In motion Green :  
Red :  
Green light on, Red light on
Inposition deviation Green :  
Red :    
Green and Red light alternately flashing
Alarm Green :  
Red :  
Red light flashing repeatedly as many as alarm number
◆ Protection functions and LED flash times
Times Protection Conditions
1 Over Current Error The current through power devices in inverter exceeds the 4.8A
2 Over Speed Error Motor speed exceed 3,000 [rpm]
3 Position Tracking Error Position error value is higher than 180˚ in motor run state*1
4 Over Load Error The motor is continuously operated more than 5 seconds under a load exceeding the max. torque
5 Over Temperature Error Inside temperature of drive exceeds 85℃
6 Over Regeneratived Voltage Error Back-EMF is more than 48V value
7 Motor Connect Error The power is ON without connection of the motor cable to dreiv
8 Encoder Connect Error Cable connection error with Encoder connection in drive
10 In-Position Error After operation is finished, a position error occurs
12 ROM Error Error occurs during tuning execution
15 Position Overflow Error Position error value is higher than 180˚ in motor stop state*1
  • * 1 : Default value can be changed by parameter(Refer of the Manual)
Alarm LED flash
(Ex, Position Tracking Error)

Setting & Connector

1. Termination Setting
When pin 9 and pin 10 of the connector(CN1) aer connected externally, the drive is set to the end of the network. If the drive is connected to the end of the communication network, set it to the termination.
2. Network ID Setting
The network ID of Ezi-SERVO-ALL-28 series can be set using Ezi-MOTION Plus-R GUI(Version 6.40.7.12 or later). After connecting the communication, the seting window appears by selecting the product and press the right button of the mouse.
3. Input/Output Signal Connector(CN1)
No. Function I/O
1 GND Input
2 24VDC Input
3 IO COMMON Input
4 ORIGIN Input
5 LIMIT+ Input
6 LIMIT- Input
7 In1 Input
9 Termination Input
10 Data- Communication
11 Data+ Communication
12 S-GND Input

Connector Specifications

Connector specifications for cabling to drive.
Purpose Item Part Number Manufacturer
Signal Housing
Terminal
GHR-12V-S
SSHL-005T-P0.2
JST
※ Above connector is the most suitable product for the drive applied. Another equivalent connector can be used.

Ezi-SERVO ALL-42/56 Series

Status Monitor LED

◆ Protection functions and LED or 7-Segment flash times
When Alarm occurs, can recognize main reason of alarming thru by LED or 7-Segment flash times.
Times Protection Conditions
1 Over Current Error The current through power devices in inverter exceeds the 4.8A
2 Over Speed Error Motor speed exceed 3,000 [rpm]
3 Position Tracking Error Position error value is higher than 180˚ in motor run state*1
4 Over Load Error The motor is continuously operated more than 5 seconds under a load exceeding the max. torque
5 Over Temperature Error Inside temperature of drive exceeds 85℃
6 Over Regeneratived Voltage Error Back-EMF is more than 48V value
7 Motor Connect Error The power is ON without connection of the motor cable to dreiv
8 Encoder Connect Error Cable connection error with Encoder connection in drive
10 In-Position Error After operation is finished, a position error occurs
12 ROM Error Error occurs during tuning execution
15 Position Overflow Error Position error value is higher than 180˚ in motor stop state*1
  • * 1 : Default value can be changed by parameter (Refer to the Manual)
7-Segment flash
(Ex, Position tracking error)

Switch

1. Termination Setting Switch(SW1)
The drive installed at the end of the network must be terminated for reliable operation. Please termination setting switch is ON if drive installed at the end of the network.
2. Network ID Setting Switch(SW2)
Position ID Number
0 0
1 1
2 2
3 3
4 4
5 5
6 6
7 7
Position ID Number
8 8
9 9
A 10
B 11
C 12
D 13
E 14
F 15
※ Maximum 16 axis can be connected in one network.
3. Communication Speed Setting Switch(SW3)
The purpose of this is to seting the communication speed
SW3.1 SW3.2 SW3.3 Baud Rate [bps]
OFF OFF OFF 9,600
ON OFF OFF 19,200
OFF ON OFF 38,400
ON ON OFF 57,600
OFF OFF ON 115,200*1
ON OFF ON 230,400
OFF ON ON 460,800
ON ON ON 921,600
* 1 : Default setting value
* 2 : SW3.4 is not available to use

Connector

1. Input/Output Signal Connector(CN1)
No. Function I/O
1 EXT_24VDC Input
2 EXT_GND Input
3 BRAKE+ Output
4 BRAKE- Output
5 LIMIT+ Input
6 LIMIT- Input
7 ORIGIN Input
8 Digital In1 Input
No. Function I/O
9 Digital In2 Input
10 Digital In3 Input
11 Digital In4 Input
12 Digital In5 Input
13 Digital In6 Input
14 Digital In7 Input
15 Compare Out Output
16 Digital Out1 Output
2. Power Connector(CN2)
No. Function I/O
1 24VDC Input
2 GND Input
3. RS-485 Communication Connector(CN3, CN4)
No. Function
1 Data+
2 Data-
2 GND

Connector Specifications

Connector specifications for cabling to drive.
Purpose Item Part Number Manufacturer
Power
(CN2)
Terminal Block AK155012F-3.81 PTR
Signal
(CN1)
Housing
Terminal
501646-1600
501648-1000(AWG 26~28)
MOLEX
RS-485 Communication
(CN3, CN4)
Housing
Terminal
35507-0300
50212-8100
MOLEX
※ Above connector is the most suitable product for the drive applied. Another equivalent connector can be used.

Ezi-SERVO ALL-60/60-ABS Series

Status Monitor LED

◆ Protection functions and LED or 7-Segment flash times
When Alarm occurs, can recognize main reason of alarming thru by LED or 7-Segment flash times.
Times Protection Conditions
1 Over Current Error The current through power devices in inverter exceeds the 4.8A
2 Over Speed Error Motor speed exceed 3,000 [rpm]
3 Position Tracking Error Position error value is higher than 180˚ in motor run state*1
4 Over Load Error The motor is continuously operated more than 5 seconds under a load exceeding the max. torque
5 Over Temperature Error Inside temperature of drive exceeds 85℃
6 Over Regeneratived Voltage Error Back-EMF is more than 48V value
7 Motor Connect Error The power is ON without connection of the motor cable to dreiv
8 Encoder Connect Error Cable connection error with Encoder connection in drive
10 In-Position Error After operation is finished, a position error occurs
12 ROM Error Error occurs during tuning execution
15 Position Overflow Error Position error value is higher than 180˚ in motor stop state*1
  • * 1 : Default value can be changed by parameter (Refer to the Manual)
Alarm LED or 7-Segment flash
(Ex, Position tracking error)

Switch

1. Network ID Selection Switch(SW1)
Position ID Number
0 0
1 1
2 2
3 3
4 4
5 5
6 6
7 7
Position ID Number
8 8
9 9
A 10
B 11
C 12
D 13
E 14
F 15
※ Maximum 16 axis can be connected in one network.
※ Ezi-SERVO-ALL-60 series only.
※ The network ID of Ezi-SERVO-ALL-60-ABS can be set under RS-485 commuication
2. Speed and Termination Setting Switch(SW3)
◆ Ezi-SERVO-ALL-60 series
Termination Setting Switch(SW1.4)
The drive installed at the end of the network must be terminated for reliable operation. Please termination setting switch is On if drive installed at the end of the network.

Speed Setting Switch(SW1.1~SW1.3)
SW1.1~ SW1.3 used for setting speed as follows
SW1.1 SW1.2 SW1.3 SW1.4 Baud Rate [bps]
OFF OFF OFF - 9,600
ON OFF OFF - 19,200
OFF ON OFF - 38,400
ON ON OFF - 57,600
OFF OFF ON - 115,200*1
ON OFF ON - 230,400
OFF ON ON - 460,800
ON ON ON - 921,600
* 1 : Default setting value

Connector

1. Power Connector(CN3)
No. Function I/O
1 24VDC Input
2 24VDC Input
3 GND Input
4 GND Input
2. RS-485 Communication Connector(CN5, CN6)
No. Function
1 Data+
2 Data-
3 GND
3. Input/Output Signal Connector(CN1)
NO. Ezi-SERVO ALL-60 Series Ezi-SERVO ALL-60L-ABS Series
Function I/O Function I/O
A EXT_24VDC Input EXT_24VDC Input
B EXT_GND Input EXT_GND Input
C LIMIT+ Input LIMIT+ Input
D LIMIT- Input LIMIT- Input
E ORIGIN Input ORIGIN Input
F Digital In1 Input Digital In1 Input
G Digital In2 Input Digital In2 Input
H Digital In3 Input Digital In3 Input
I Digital In4 Input Digital In4 Input
K Digital In5 Input Digital In5 Input
L Digital In6 Input Digital In6 Input
M Digital In7 Input Digital Out1 Output
N Compare Out Output Digital Out2 Output
O Digital Out1 Output Digital Out3 Output
P Digital Out2 Output Digital Out4 Output
R Digital Out3 Output Digital Out5 Output
S NC Output Digital Out6 Output
T BRAKE+ Output BRAKE+ Output
U BRAKE- Output BRAKE- Output

Connector Specifications

Connector specifications for cabling to drive.
Purpose Item Part Number Manufacturer
Power
(CN2)
Connector 99-0410-00-04 BINDER
Signal
(CN1)
Connector 99-5461-40-19 BINDER
RS-485 Communication
(CN3, CN4)
Connector 99-0405-00-03 BINDER
※ Above connector is the most suitable product for the drive applied. Another equivalent connector can be used.